MIC-05s1
– USER MANUAL
34
3.3.1 Measurement of resistance of protective conductors and equipotential
bonding with ±200 mA current
Set the rotary switch at the
R
CONT
position.
The meter is ready for meas-
urement. Press
F4
to
set the maximum resistance
value.
The value may be set in the range from 0.01
Ω to 999 Ω.
Connect the meter to the tested object. Begin the measurement
by pressing
START
.