OPERATING MANUAL MIC-10s1 version 1.03
60
Measurement of continuity of protective conductors and equipotential bonding with
200 mA
current
Measuring range according to IEC 61557-4: 0.12
…999
Display range
Resolution
Basic uncertainty
0.00
to
19.99
0.01
±(2 % m.v. + 3 digits)
20.0
to 199.9
0.1
200
to
999
1
±(4 % m.v. + 3 digits)
Voltage at open terminals: 4 V
to 24 V
Output current at R<15
: min. 200 mA (I
SC
: 200 mA
to 250 mA)
Current flowing bi-directionally, average resistance is displayed on the screen,
Compensation of test leads resistance, autozeroing.
Temperature Measurement
Display range
Resolution
Basic uncertainty
-40.0
to
99.9
°
C
0.1
°
C
±(3% m.v. + 8 digits)
-40.0
to
211.8
°
F
0.1
°
F
±(3% m.v. + 16 digits)
Other technical data
a) insulation .................................................. double-insulated, EN 61010-1 and IEC 61557 compliant
b) measurement category .............................CAT IV 600 V (CAT III 1000 V) according to EN 61010-1
c) degree of housing protection acc. to EN 60529.............................. IP40 (IP67 for closed enclosure)
d) power supply of the meter............................ 14.8 V 5.3 Ah Li-Ion battery, 90 V - 260 V 50 Hz/60 Hz
e) dimensions ................................................. 15.4 in x 12.2 in x 6.3 in / 390 mm x 310 mm x 180 mm
f) meter weight ............................................................................................... approx. 12.3 lbs / 5.6 kg
g) storage temperature ...................................................................... -12
F to 158
F /
–25
C to +70
C
h) working temperature ....................................................................... -4
F to 122
F / -20
C to +50
C
i)
humidity ........................................................................................................................ 20% to 90%
j)
altitude (above sea level) ...................................................................................................
≤3000 m
k) reference temperature ........................................................................... 73
F ± 1.6
F / +23
C ± 2
C
l)
reference humidity ........................................................................................................ 40% to 60%
m) display ............................................................................................................................... TFT LCD
n) number of R
ISO
measurements, acc. to EN 61557-2 with battery power supply ................. min. 1000
o) design, construction and manufacturing are ISO 9001, ISO 14001, PN-N-18001 compliant
p) the device meets the requirements of the EN 61010-1 and IEC 61557 standards
q) the product meets EMC requirements (immunity for industrial environment) according to the
following standards ........................................................ EN 61326-1:2006 and EN 61326-2-2:2006
ATTENTION!
MIC-10s1 meter is classified in terms of Electromagnetic Compatibility (EMC)
as instruments of Class A (for use in industrial environments - according to EN
50011). Interference may affect the operation of other devices used in other
environments (e.g. domestic).
Summary of Contents for MIC-10s1