MMR-650 – USER MANUAL
30
When measuring inductive ob-
jects, only Auto mode is avail-
able - the measuring current is
limited to a value not exceed-
ing the set value,
Setting the measuring current
limits.
Use
button to go to the next settings.
Selection of
measurement
mode:
- normal
- continuous:
the measure-
ment continues
until it is turned
off by pressing
START/STOP
button
Switching Unidirec-
tional/Bidirectional
measurement.
Algorithm selection:
- normal
- fast: greater toler-
ance for result stabil-
ity criterion
- special – can be
used among others
for amorphous cores.
Boxes for setting the range and measurement current on the screen above correspond to the same
boxes shown in the previous screen.
Note:
- Bidirectional measurement is used to compensate the potential present at the contact point of two
different conductors. In this case, the main result of the measurement is the average of results from
individual directions.
- Amorphous core is made of amorphous sheet, which has a non-crystalline structure that is closer to
glass than metal. No-load losses in such a transformer are much lower than in traditional transformers.
The process of measuring the resistance, due to the nature of the object, contains a measurement
algorithm modified in relation to normal inductive objects.