MPI-525
– USER MANUAL
21
Press F1 push-button to change test voltage.
Select test voltage by means of push-buttons and
confirm by pressing
ENTER
.
Press
START
push-button to start the measurement.
Read out the result.
Resistance of current electrode
Resistance of voltage electrode
Value of additional uncertainty
caused by resistance of the elec-
trodes
S
Repeat the measurements (points 3, 7, 8) shifting the volt-
age electrode several metres: the electrode should be
shifted farther and closer to the earth electrode being
tested. If R
E
measurement results differ from one another
by more than 3%, the distance of the current electrode
from the earth electrode being tested should be consider-
ably increased and the measurements should be re-
peated.