MPI-525
– USER MANUAL
23
3.5 Measurement of RCD parameters
Attention:
Measurement of U
B
, R
E
is always conducted with the use of sinusoidal current 0.4I
n
regardless
of the settings concerning waveform and multiplication factor I
n
.
3.5.1 Measurement of RCD trip current
Set the rotary switch of function selection at
I
A
position.
Press
F1
I
n
push-button
and move to I
n
selection.
Press
F2
push-button
and move to selection of cur-
rent waveform.
Press
F3
G S
push-button
and move to selection of RCD
type.
Select an appropriate item by means of
and
push-
buttons and confirm by pressing
ENTER
.
Move to selection of a second group of parameters by
means of
and
push-buttons.
Press
F1
U
L
push-button
and move to selection of U
L
.
Press
F2
MODE
push-button
and move to selection of
measurement mode.