MPI-525
– USER MANUAL
32
Connect test leads according to the drawing.
Press and hold
START
push-but-
ton.
Measurement is performed continu-
ously when the push-button is held
in the pressed position.
In order to maintain the
measurement, press
ENTER
push-
button while holding
START
push-
button in the pressed position. In
order to interrupt the mesaurement,
press
START
push-button again.
View of the screen
during measurement
performed with the
use of
ENTER
push-
button.
At the end of the particular time period the current value of the insulation re-
sistance (designated as R
t1
, R
t2
or R
t3
according to the time period that has
expired) is displayed. Absorption coefficients are calculated as:
Ab1 = DAR = R
t2
/
R
t1
and Ab2 = PI = R
t3
/ R
t2
.
Read out the result.