MPI-525
– USER MANUAL
34
Press
F1
U
N
push-button
and move to selection of
nominal test voltage U
N
.
Press
F2
TIME
push-button
and move to selection
of a single measurement
time.
Press
F3
MODE
push-button
and move to selection of lead
or energetic cable type (3-, 4-
or 5-cores lead).
Select an appropriate item by means of
and
push-buttons and confirm by pressing
ENTER
.
Connect AutoISO-2500 adapter to the lead tested.
Press
START
push-buttons to start measurement. First,
checking of voltages on particular pairs of cores is per-
formed.
If any of the voltages exceeds allowable voltage, the sym-
bol of this voltage with
“!” mark is displayed (e.g. U
N-PE
!) and
the measurement is aborted.