MRU-120
– USER MANUAL
24
3.6 Earth resistance measurement with two-clamp method (2C)
Two-clamp measurements are applied where there is no possibility of using ground-driven elec-
trodes.
NOTE!
The two-clamp method may be used solely in the case of
multiple earthing measurements.
Turn the meter on.
Set the rotational
function selector at
.
CA
T
IV
3
00
V
H
E
C-3
N-1
Connect the transmission clam to sockets
H
and
E
, while the measurements clamp
should be connected to the clamp socket.
Snap the transmission clamp and measurement clamp on the tested earth elec-
trode AT east 30 cm from each other.
The meter is ready for measurement.
Press
START
In order for the test to com-
mence measurement.