MRU-200-GPS OPERATING MANUAL Version 1.06
14
then connect the meter to the computer. Select
Software upgrade
in the MENU and follow the on-
screen instructions.
2.5 Language choice
Use and buttons to select
**Language choice**
in the main MENU and press
ENTER
.
Use and buttons to select the language and press
ENTER
.
2.6 Information on the manufacturer
Use and buttons in order to select
Product info
and press
ENTER
.
3
Measurements
Note:
During measurements the status bar is displayed.
3.1 Measurement of earth connection and equipotential bonding
(2P)
Note:
The measurement complies with the requirements specified in the norm
EN 61557-4 (U<24V, I>200mA or R
≤
10
Ω).
Turn the meter on.
Set the rotary
function selector switch at
2P
.
Connect the earth ground system to be measured to the terminals
S
and
E
of the
meter.