MRU-200-GPS OPERATING MANUAL Version 1.06
18
Turn the meter on.
Set the rotary
function selector switch at
3P
.
E
S
H
CA
T
IV
3
00
V
Drive the current probe into the ground and connect to the
H
socket of the meter.
Drive the voltage probe into the ground and connect to the
S
socket of the meter.
Connect the earth ground electrode under test to the E socket of the meter.
Align all electrodes in a straight line.
The meter is ready for measurement.
The auxiliary display shows the value of
the interference voltage and its fre-
quency. The settings bar shows the
mains frequency set in the MENU.
Press
F1
to select the measuring
voltage.