MRU-200-GPS OPERATING MANUAL Version 1.06
26
Press
START
to begin measurement.
View the result.
Current probe resistance
Voltage probe resistance
Additional uncertainty caused by
the resistance of the probes.
Press the
F4
button to display GPS coordinates.
The result is displayed for 20s.
It may be displayed again when
ENTER
is pressed.
S
Repeat the measurements a few times (see points 2 and 5)
each time moving the voltage probe a few feet / a couple of
meters, both to and away from the tested earth ground elec-
trode. If after several R
E
tests the results differ more than 3%,
then significantly increase the distance between the current
electrode from the earth electrode under test, and repeat the
measurement procedure again.
Notes:
Flexible Rogowski current probes must not be used for this measurement.