MRU-200-GPS OPERATING MANUAL Version 1.06
30
Use , buttons to select the number
of pylon legs, press
ENTER
.
Press
START
. Follow the command on the
screen and position the current probe
around the first leg of the pylon (if not al-
ready done).
To start the measurement, press
START
again.
After the measurement of the first leg of the pylon, the measured re-
sistance value of the tested leg is shown on the main screen as R1.
After 5 seconds the meter transfers the R1 result to the window on the
right side of the display and displays a message to attach the current
probe around the next leg of the pylon.