MRU-200-GPS OPERATING MANUAL Version 1.06
31
The last result may be restored on the display for another 5 seconds by
pressing
ENTER
.
After performing the measurement on the last leg of the pylon the
meter displays the last result for 5 seconds, the meter will then
display the resultant earth resistance R
E
.
Use buttons
and
to change results displayed in the window on
the right side of the screen.
3.7 Two-clamp measurement
Two-clamp measurements are used where there is no possibility of using ground-driven elec-
trodes.
NOTE!
The two-clamp method may be used solely in the case of multiple earthing
measurements.
Turn the meter on.
Set the rotary function se-
lector switch at
.