MRU-200-GPS OPERATING MANUAL Version 1.06
32
CA
T
IV
3
00
V
H
E
C-3
N-1
Connect the transmission clamp to sockets
H
and
E
. The measurement clamp
should be connected to the clamp socket.
Attach both the transmission clamp and the measurement clamp on the earth
ground electrode under test at least 1 ft. / 30cm from each other as shown.
The meter is ready for measurement.
The auxiliary display shows the value of the
leakage current passing through the
measurement clamp with split core (C-3)
and its frequency.
Press
START
to begin measurement.
View the result.
The result is displayed for 20s. It may be displayed again when
ENTER
is pressed.
Notes:
Measurements may be performed in the presence of interference current not
exceeding 3A rms and whose frequency complies with the value set in the
MENU.