MRU-200
● MRU-200-GPS – USER MANUAL
15
3
Measurements
Note:
During measurements the status bar is displayed.
3.1
Measurement of resistance of earth connection and equipotential
bonding (2P)
Note:
The measurement complies with the requirements specified in the norm EN 61557-4
(U<24 V, I>200 mA for R
≤
10
Ω).
Turn the meter on.
Set the rotational
function selector at
2P
.
Connect the object being measured to the terminals
S
and
E
of the meter.
The meter is ready for measurement.
The auxiliary display shows the value
of the interference voltage and its fre-
quency. The setting bat shows the
mains frequency set in the MENU.