MRU-200
● MRU-200-GPS – USER MANUAL
16
Press
START
In order for the test to
commence.
Read out the result.
The right side of the display
shows the date, time and GPS coordi-
nates.
The result is displayed for 20 s.
It may be displayed again when
ENTER
is pressed.
Additional information displayed by the meter
R>19,99k
Ω
Measurement range exceeded.
U
N
>40V!
and a con-
tinuous sonic signal
The voltage on the measurement points exceeds 40 V,
the measurement is blocked.
U
N
>24V!
The voltage on the measurement points exceeds 24 V
but lower than 40 V, the measurement is blocked.
NOISE
!
The value of the interfering signal is too high,
the result may be distorted by additional uncertainty.
3.2
Calibration of the test leads
In order to eliminate the influence of the resistance of the test leads over the result of the meas-
urement, it is possible to realize its compensation (auto-zeroing). In order to do so the measurement
function
2P
includes the
AUTOZERO
subfunction.
3.2.1 Auto-zeroing on
Turn the meter on.
Set the rotational
function selector at
2P
.
Press
F1
.