MRU-200
● MRU-200-GPS – USER MANUAL
34
Turn the meter on.
Set the rotational
function selector at
4P
.
ES
S
C
AT
IV
3
00
V
H
E
Connect the current electrode driver into ground to the
H
socket of the meter.
Connect the voltage electrode driver into ground to the
S
socket of the meter.
Connect the tested earth electrode to the
E
socket and the shield of the
H
ca-
ble.
Connect the
ES
socket to the earth electrode in question below the
E
cable.
The tested earth electrode and the current electrode and voltage electrode should be
placed in such a manner than the angle between the gauging aligned amount to
60°
.
The meter is ready for measurement.
The auxiliary display shows the value of
the interference voltage and its frequen-
cy. The setting bar shows the pulse build
up time.
Press
F1
in order to modify the pulse
shape.