MZC-304
– USER MANUAL
33
Other technical specification
a) type of insulation ..................................................... double, EN 61010-1 and IEC 61557 compliant
b) measurement category ................................................... IV 300V (III 600V), EN 61010-1 compliant
c) degree of protection of enclosure acc. to EN 60529 ................................................................. IP67
d) meter power supply ............. LR6 alkaline batteries or NiMH rechargeable batteries size AA (4 pcs)
e) dimensions .............................................................................................................. 220x98x58 mm
f) meter weigth ................................................................................................................. about 0.6 kg
g) storage temperature .....................................................................................................
–20...+70
C
h) operating temperature ...................................................................................................... 0...+50
C
i)
humidity ............................................................................................................................. 20...90%
j)
reference temperature .....................................................................................................
+23 ± 2
C
k) reference humidity ............................................................................................................. 40...60%
l)
altitude (above sea level) ................................................................................................... <2000 m
m) time to Auto-OFF ......................................................................................................... 120 seconds
n) number of measurements Z (for rechargeable batteries) ........ >5000 (2 measurements per minute)
o) display ........................................................................................................................LCD segment
p) memory of measurement results ................................................................ 990 cells, 10000 entries
q) data transmission ...................................................................... radio link, waveband ISM 433 MHz
r) quality standard .......................... development, design and manufacturing are ISO 9001 compliant
s) the device meets the requirements of the IEC 61557 standard
t) the product meets the EMC requirements (immunity for industrial environment) according to the
following standards .......................................................................... EN 61326-1 and EN 61326-2-2
9.2 Additional information
Information about additional uncertainty is useful mainly when the meter is used in untypical con-
ditions and for the measurements laboratories during calibration.
9.2.1
Additional uncertainty according to IEC 61557-3 (Z)
Influencing value
Designation
Additional uncertainty
Location
E
1
0%
Supply voltage
E
2
0% (
BAT
is not displayed)
Temperature 0...35°C
E
3
1.2m lead
– 0Ω
5m lead
– 0.011Ω
10m lead
– 0.019Ω
20m lead
– 0.035Ω
WS-01, WS-05, WS-07 leads
–
0.0
15Ω
Phase angle 0..30° at the bot-
tom of measurement range
E
6.2
0,6%
Frequency 99%..101%
E
7
0%
Mains voltage 85%..110%
E
8
0%
Harmonics
E
9
0%
DC component
E
10
0%
9.2.2
Additional uncertainty according to IEC 61557-4 (R
±200 mA)
Influencing value
Designation
Additional uncertainty
Location
E
1
0%
Supply voltage
E
2
0,5% (
BAT
is not displayed)
Temperature 0...35°C
E
3
1,5%