PQM-700 Operating Manual
20
In systems with neutral conductor, the user may additionally activate current measurement in
this conductor, after installing additional clamps in I
N
channel. This measurement is performed after
activating in settings the option of
Current in N conductor
.
Note
In order to correctly calculate total apparent power S
e
and total Power
Factor (PF) in a 4-wire 3-phase system, it is necessary to measure the
current in the neutral conductor. Then it is necessary to activate option
Current in N conductor
and to install 4 clamps as shown in Fig. 7. More
information may be found in sec. 6.4.5.
Pay attention to the direction of current clamps (flexible and CT). The clamps should be installed
with the arrow indicating the load direction. It may be verified by checking an active power meas-
urement - in most types of passive receivers active power is positive. When clamps are incorrectly
connected, it is possible to change their polarity using
Sonel Analysis
software.
The following figures show schematically how to connect the analyzer to the tested network
depending on its type.
Fig. 5. Wiring diagram
– single phase.