On the other hand, the power quality tests are usually made according to the EN 50160. In this
case, the analysis is carried out over a longer period of time (e.g. 7 days), and therefore the chosen
averaging time is also long - 10 minutes.
Please note that there is no single best setting for both the averaging time and other parameters
or event thresholds. Each mains system is different and so are the goals of the mains tests. There-
fore, the optimal configuration of the analyzer may require several approaches and will also depend
on the experience of the operator.