PQM-700 Operating Manual
80
maximum measured conductor diameter:
39 mm
probe lead length:
1.5 m
operating temperature:
–10
C…+55
C
humidity:
85% RH
height:
2000 m
electromagnetic compatibility:
IEC 61000-6-3:2008
IEC 61000-6-2:2008
8.3.3 C-6(A) current probe
The C-6(A) is used to measure the alternating
current with frequencies up to 10 kHz in the
10
mA…10 A range.
The output signal is voltage proportional to the
measured current with the 100 mV/A sensitivity.
The output signal is supplied by a 1.5-meter lead
with a pin adapted for the socket in the meter.
The arrow located on one of the jaws indicates
the current flow direction. It is assumed that the cur-
rent is flowing in the positive direction if it is flowing
from the source to the receiver. Such probe orien-
tation is required for a correct power measurement.
Clamps with letter 'A' at the end of marking (e.g. C-6A) are clamps with automatic type detection
in compatible devices. Other parameters are the same as in the case of clamps without automatic
clamp type detection.
Warning
Do not use the device on non-insulated conductors with a potential of
more than 600 V in relation to the earth and a measurement category
greater than III.
Reference conditions
Temperature:
+20…+26°C
Relative humidity:
20…75%
Conductor position:
conductor centered in jaws
Sinusoidal current frequency:
48…65 Hz
Harmonics content:
<1%
Current DC component:
none
Continuous magnetic field:
earth field (<40 A/m)
Alternating magnetic field:
none
Conductors in direct vicinity:
no flowing current
Technical specification
Accuracy
Current range
Basic uncer-
tainty
1)
Phase error
0.01…0.1 A
3% + 1 mA
not specified
0.1…1 A
2.5%
5
1…12 A
1%
3
1)
as % of measured value
Fig. 3. C-6(A) probe.