1 General Information
9
Fig. 2. The rear wall of PQM-700 analyzer.
Recorded parameters are divided into groups that may be independently turned on/off for re-
cording purposes and this solution facilitates the rational management of the space on the memory
card. Parameters that are not recorded, leave more memory space for further measurements.
PQM-700 has an internal power supply adapter operating in a wide input voltage range
(10
0…415 V AC / 140…415 V DC), which is provided with independent cables terminated with
banana plugs.
An important feature of the device is its ability to operate in harsh weather conditions
– the
analyzer may be installed directly on electric poles. The ingress protection class of the analyzer is
IP65, and operating temperature ranges from -
20°C to +55°C.
Uninterrupted operation of the device (in case of power failure) is ensured by an internal re-
chargeable lithium-ion battery.
The user interface consists of five LEDs and 2 buttons.
The full potential of the device may be released by using dedicated PC software
Sonel Analysis
.
Communication with a PC is possible via USB connection, which provides the transmission
speed up to 921.6 kbit/s
1.3
Power supply of the analyzer
The analyzer has a built-in power adapter with nominal voltage range of 10
0…415 V AC /
1
40…415 V DC (90…460 V AC / 127…460 V DC including fluctuations). The power adapter has
independent terminals (red cables) marked with letter P (
power
) To prevent the power adapter from
being damaged by undervoltage, it automatically switches off when powered with input voltages
below approx. 80 V AC (110 V DC).
To maintain power supply to the device during power outages, the internal rechargeable battery
is used. It is charged when the voltage is present at terminals of the AC adapter. The battery is able
Summary of Contents for PQM-700