background image

Page 2 of 3 

UK Sales Tel: 0845 345 7253 

International Tel: +44 1732 861225 

SD-521 

Issue: 5.8 

Date Of Issue: 02/06/2010 

© 2010 Sontay Limited. All rights reserved. 

Technical Overview 

Recommendations (continued)  

The SD-521 provides an auto or manual reset relay output 
on detection of smoke, with a user adjustable threshold. An 
analogue output can transmit smoke and service alarms to a 
BEMS system. 
 

Description  

 
The SD-521 duct smoke detector has been developed from a 
proven design using modern devices to provide effective and 
reliable detection of smoke in ventilation systems.  
 
Detection of smoke is achieved by monitoring a carefully 
controlled infra red beam within a perforated tube which is 
inserted into the ductwork. This method senses smoke   
directly within the duct eliminating the problems associated 
with conventional detectors mounted in sampling boxes. 
  
Circuitry incorporated in the design of the detector controls 
the infra red beam continuously. This ensures that the   
detectors  response  will  remain  constant  throughout        
operation of the system. External  influences  including    
background pollution, airborne dust and low level electrical 
interference frequently found in commercial and industrial 
applications, a common source of problems with some other 
types of   detector, are selectively filtered by the electronics 
thereby providing the highest sensitivity to smoke combined 
with effective rejection of short term disturbances that 
would otherwise give a false alarm.  
 
The detector features variable sensitivity and an advanced 
signal damping circuit which can be bypassed for testing 
purposes.  And this signal is available as an analogue output 
to communicate with a building management system.  
 

Recommendations 

 
The SD-521 has a probe length of 300mm and should NOT 
be used in ducts with a diameter or square size greater than 
450mm, as it will not monitor the whole of the duct and 
smoke may pass along the duct without being detected. 
 
Units should NOT be mounted where ambient sunlight will 
fall on the photocell. 
 
Units should never be mounted at or near sharp bends in 
ductwork, as turbulence and side currents can carry the 
smoke away from the probe.  
 
The SD-521 is an optical beam detector and therefore, air 
velocity  has  little  effect  on  performance.  However,  careful 
positioning of the detector is required if optimum detection  

is to be achieved. The detector should always be fitted with 
the holes in the sensing tube parallel to the airflow. 

 

Units should to be mounted close to supply or extract fans. 

 

With large installations, where several ducts collect into a 
common duct, consideration must be given to dilution of 
smoke and rate of airflow. For example, 10 small ducts may 
feed at different points into one large main extract duct, and 
if only one smoke detector is fitted in the main extract duct, 
the position can arise where one duct is feeding smoke and 
nine are feeding clean air. The amount of smoke is therefore 
diluted by 90%, and if this is coupled with a high flow rate, 
the smoke may not be detected for the minimum operating 
period of 1 second, resulting in no alarm being generated. It 
may be necessary to mount 10 detectors in each of the 
small ducts to guarantee correct operation. 
 

Installation Notes 

 
Removable links are provided for signal damping and     
internal latching of the output relay. 
 
It  is  recommended  that  the  damping be used (LK1) for   
normal use as this will give the best false alarm rejection. 
The link should be removed for testing purposes. 
 
The internal latching circuit is enabled with the link LK2 in 
place, in this condition any alarm will result in the detector 
signal remaining on until locally reset. If the latching link is 
removed and conditions return to normal for this reason the 
electrical circuit to which the detector is connected should 
have self latch with reset facilities. 
 
Due to the self calibrating design of the detector as dust 
builds up on the optics the internal signal is increased to 
compensate, this results in the detector maintaining 

 

 

 

 

 

sensitivity during operation. Failure to clean the detector will 
ultimately result in an alarm signal occurring. At the final 
signal level, either from dust accumulation or dense smoke 
the detector will remain in alarm state for a minimum of 1 
minute, following this final stage the detector will not be 
able to recalibrate and will no longer function correctly.  
 
As with all detectors it is not recommended to switch fan or 
damper loads directly as any fire in the vicinity may damage 
the detector or the wiring resulting in loss of control.  
 
 
 
 

Reviews: