16
Instruction for use | Supercal 5
4.5 Dimensions
159.6
163.6
136.3
138.3
49
5.5
23.2
175.1
95.08
143
158
53.5
3.9
4.6 Mounting
4.6.1 Before Mounting
All cables must be laid at a
minimum distance of 300 mm
from power
and high-frequency cables.
Radiant heat and electrical interference fields in the vicinity of the
calculator must be avoided.
The calculator must generally be mounted separately from the heat or
cold pipe.
It must be ensured that no condensation water can run into the
calculator along the connected lines.
If there is a risk of vibrations in the piping system, the calculator should
be mounted separately on the wall.
For medium temperatures above 90°C, the calculator should be
mounted separately.
The flow sensor should be mounted between two shut-off valves.
For the flow sensor, the direction of flow must be observed (arrow on
the flow sensor).
The pipeline must be flushed before mounting the flow sensor to ensure
that there are no foreign bodies in the pipeline.
The lines must be vented during commissioning. Air in the system or in
the flow sensor can impair the measurement result.
Only use suitable new sealing material.
The tightness of the various connections must be checked.
Lightning protection cannot be guaranteed; this must be ensured via
the house installation.