18
Instruction for use | Supercal 5
4.6.3 Top Hat Rail Mounting
Monté
Installation
4.7 Installation Instructions For Temperature Sensors
When selecting and installing temperature sensors, the greatest care must be taken. Errors
committed here can no longer be compensated even by the best calculator
CAUTION
Take care when installing the temperature sensors!
Incorrect removal of directly immersing temperature sensors may result in an acci-
dent! Installation and removal may only be carried out by authorized and competent
persons.
NOTICE
Shielding of the cables against electromagnetic interference!
If there is a danger of electrical or electromagnetic interference, temperature sensors
in 2- and 4-wire technology with shielded cables or shielded cables at the connection
heads must be used. The shielding should be connected to the appropriate electrical
ground in the calculator. The possibility of interference increases with the length of
the sensor cables!
The connection cables must not be separated, extended or shortened!
The sensors are exactly computer paired in the factory and may only be used in the
original pairing!
Installation with cable lengths over 3 m
For installations with cable lengths over 3 m or with unequal cable lengths,
we recommend the use of 4-wire temperature sensors. The maximum cable
length of the 4-wire temperature sensors is 50 m