13
Installation
The controller operates with Pt1000 temperature sensors which are accurate to the
degree, thus ensuring optimal control of system functions.
C.3 Installing the temperature sensors
Caution
Position the sensor precisely in the area to be measured!
Only use immersion, pipe-mounted or fl at-mounted sensors suitable
for the specifi c area of application with the appropriate permissible
temperature range.
Caution
The line of S1 can be extended if needed to a maximum of 30m using a
cable with a cross-section of at least 0.75mm². The lines of S2 and S3
can be extended if needed to a maximum of 10m using a cable with a
cross-section of at least 0.75mm².
Make sure that there is no contact resistance!
Caution
The temperature sensor cables must be routed separately from
mains voltage cables, and must not, for example, be routed in the
same cable duct!