7.2.4. - PWM off
This signal is put out when the pump is switched off (Pumps that can detect cable
break need a minimum signal).
Settings range: (Solar:) 0 to 50% / Default setting: 0% - (Heating:) 50% to 100% /
Default setting: 100%
7.2.5. - PWM on
This signal is needed to turn the pump on at minimum speed.
Settings range: (Solar:) 0 to 50% / Default setting: 10% - (Heating:) 50% to 100% /
Default setting: 90%
7.2.6. - PWM Max
This determines the output signal for the highest speed of the pump, that is used e.g.
during purging or manual operation.
Settings range: (Solar:) 50 to 100% / Default setting: 100% - (Heating:) 0% to 50% /
Default setting: 0%
When Output signal PWM is selected:
When Output signal 0-10V is selected:
7.2.4 - 0-10V off
This voltage is put out when the pump is turned off (Pumps that can detect cable break
need a minimum voltage).
Settings range: (Solar:) 0,0 to 5,0 V / Default setting: 1,0 V - (Heating:) 5,0 to 0,0 V /
Default setting: 4 ,0 V
7.2.5 - 0-10V on
This voltage is needed to turn the pump on at minimum speed.
Settings range: (Solar:) 0,0 to 5,0 V / Default setting: 1,0 V - (Heating:) 5,0 to 10,0 V /
Default setting: 9,0 V
7.2.6 - 0-10V Max
This determines the output voltage for the highest speed of the pump, that is used e.g.
during purging or manual operation
Settings range: (Solar:) 5,0 to 10,0 V / Default setting: 10,0 V - (Heating:) 0,0 to 5,0 V /
Default setting: 0,0 V