11. Protective functions
Menu “6. Protective functions” can
be used to activate and set various
protective functions.
Caution
The menu is closed by pressing
“esc” or selecting “Exit settings”.
This does not under any
circumstances replace
the safety facilities to be
provided by the customer!
11.1 Seizing protection
menu 6.1 / 6.1.1 - 6.1.2
If the seizing protection is activated, then the controller switches the relay
and the connected pump on every day at 12:00 and on Sundays at 12:00 for
5 seconds in order to prevent the pump from sticking after an extended
stationary period.
Setting range R1: daily, weekly, off/default setting: daily
11.2 Frost protection
menu 6.2 / 6.2.1 - 6.2.2
A two-stage frost protection function can be activated. In stage 1 the
controller switches the pump on for 1 minute every hour if the collector
temperature drops below the set value “Frost stage 1”.
If the collector temperature drops further to the set value “Frost stage 2” the
controller switches the pump on continuously.
If the collector temperature then exceeds the value “Frost stage 2” by 2°C,
then the pump switches off again.
Frost protection setting range: on, off/default setting: off
Frost stage 1 setting range: from -25°C to 10°C or off/default setting: 7°C
Frost stage 2 setting range: from -25°C to 8°C/default setting: 5°C
Caution
This function causes energy to be lost via the collector! It is normally
not activated for solar systems with antifreeze.
Observe the operating instructions for the other system
components!