Installation & Adjustment Procedures
Preferred Switch Assembly Method:
1.3
When insulators are shipped installed on the switch and the switch has been
adjusted at the factory, proceed to
1. Set up bearing housing with clip angles installed at ground level. Make sure clip
angles are level and secured so that the switch does not tip over when insulators
are installed.
2. Bolt insulators to rotating flanges of bearing housing.
3. Install male blade to top of insulator with mounting bolts supplied (
).
Note that male blade is on the same side as operating lever.
Figure 2: Live Parts Mounting