7
ELECTRICAL REQUIREMENTS
220 Volt
50 Amp Service
60
Hz
1
Phase
2 wire- L1, L2 & Ground – Dedicated 220V unit only
(3 Wire- L1, L2, Neutral & Ground - Utilizes 220V and 110Vac components)
No.
6 AWG
supply wire is required
No.
8 AWG
conductor is required for bonding
USE COPPER CONDUCTORS ONLY
110 Volt
20 Amp Service
60 Hz
1 Phase
2 wire- L1, Neutral, & Ground
No. 12 AWG
supply wire is required
No. 8 AWG
conductor is required for bonding
USE COPPER CONDUCTORS ONLY
It is the responsibility for the installer and the owner to install a
readily accessible disconnecting means during the installation.
MOUNTING
Per UL 1563, paragraph 6.4.3, the AP-4 Indoor Spa Pack and the additional pump
(Jets 2, optional) shall be mounted so that the lowest portion of any live part is a
minimum of 4 in. above the mounting surface.
CAUTION: THE EQUIPMENT AND CONTROLS SHALL BE LOCATED
NOT LESS THAN 5 ft (1.5M) HORIZONTALLY FROM SPA OR HOT
TUB.
ELECTRICAL RE
Q
UIREMENTS