Ozonator Does Not Work!
If ozonator isn't working, carry out the following tests to correct
the problem:
To increase the life of the relay, we use a "snubber" circuit on the ozonator relay.
With this type of circuit, if no ozonator is connected to an output and relays are open,
the voltmeter will still get a reading of around 60 volts. This is normal.
It is important to take voltage reading when ozonator is connected to pack.
Power must remain On.
Please take note that ozonator output will be shut down when Pump 1, Pump 2 or
blower have been turned on manually.
1• Verify if "Filter Cycle" indicator
appears on keypad.
2• If not, start up a filter cycle.
Press and hold
Light
key for
5 seconds.
The display
will show a
value that
represents the filter
cycle duration in hours.
Press
Light
key
again. The filter
cycle will start
immediately.
3• Measure voltage between
ozonator black and white
connectors:
240 VAC ozonator: P16 & P19
120 VAC ozonator: P16 & P8
You should read
≈
240 VAC
(
≈
120 VAC for a 120 VAC
ozonator).
4• Replace ozonator if you get a
good voltage reading.
5• Check if Pump 1 is working.
If so, replace Spa Pack.
If Pump 1 is not working, refer
to "Pump 1 does not Work!"
section.
"Filter Cycle"
indicator
Summary of Contents for SC-CF
Page 5: ...4 SC CF SC MP Service Manual...
Page 19: ...18 SC CF SC MP Service Manual...
Page 23: ...22 SC CF SC MP Service Manual...
Page 29: ...28 SC CF SC MP Service Manual...
Page 41: ...40 SC CF SC MP Service Manual...
Page 45: ...44 SC CF SC MP Service Manual...
Page 49: ...48 SC CF SC MP Service Manual...
Page 53: ...52 SC CF SC MP Service Manual...