Form 44201360
18
Oct 2019
g)
The heater must be suspended with its longitudinal axis horizontal, but may have its lateral axis at an angle
from 0° to 60° from the horizontal, as shown in the minimum clearances to combustibles section 4.0).
h)
An optional heat shield may be installed to reduce the top distance of clearance to combustibles. This heat
shield should be installed prior to hanging the heater. When using the heat shield at the minimum
clearance distance the angles of installation are restricted to 0°, 15°, 30°, 45° and 60°.
i)
Use the provided angle gauge to ensure that the heater is hung at the approved installation angles.
j)
The heater can be angle mounted on both sides of its lateral axis.
k)
Hanging brackets should first be fixed to the wall surface by means of 4 lag bolts – not supplied (M10 x
75mm minimum) through pre-formed holes in each of the brackets prior to installing heater.
HEATER MOUNTING ANGLE
12.1)
Every heater is supplied with an angle gauge. The gauge is attached with tape to the heater control side.
The angle gauge is used in combination with a level to ensure that the heater is installed at one of the mounting
angles of 0
0
, 15
0
, 30
0
, 45
0
and 60
0
.
Hold the side of the angle gauge without label flush against the glass surface. Hold a level against the other side of
the angle gauge and find the desired installation angle of the heater. Verify that the level is vertical, adjust heater
angle if needed. This process must be repeated for both ends of the heater
Note: If a heat shield is installed its location must match the heaters angle (see Section 21.0).