CHECKING GAS CONNECTIONS
WARNING: Test all gas pip-
ing and connections, internal
and external to unit, for leaks
after installing or servicing. Cor-
rect all leaks at once.
WARNING: Never use an
open flame to check for a leak.
Apply a noncorrosive leak
detection fluid to all joints.
Bubbles forming show a leak.
Correct all leaks at once.
CAUTION: Make sure exter-
nal regulator has been installed
between propane/LP supply and
fireplace. See guidelines under
Connecting Fireplace to Gas
Supply
.
PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
2. Cap off open end of gas pipe where equipment
shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve for
propane/LP gas or opening main gas valve
located on or near gas meter for natural gas
or using compressed air.
4. Check all joints of gas supply piping system.
Apply noncorrosive leak detection fluid to all
joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Reconnect fireplace and equipment shutoff
valve to gas supply. Check reconnected fittings
for leaks.
INSTALLATION
Continued
Figure
8
- Equipment Shutoff Valve
Open
Closed
Equipment
Shutoff Valve
2. Pressurize supply piping system by either
opening propane/LP supply tank valve for
propane/LP gas or opening main gas valve
located on or near gas meter for natural gas
or using compressed air.
3. Check all joints from gas meter to equipment
shutoff valve for natural gas or propane/LP
supply to equipment shutoff valve for propane/
LP . Apply noncorro
sive leak detection fluid
to all joints. Bubbles
forming shows a leak.
4. Correct all leaks at once.
PRESSURE TESTING FIREPLACE GAS
CONNECTIONS
1. Open equipment shutoff valve (see Figure
8
).
2. Open main gas valve located on or near gas
meter for natural gas or open propane/LP
supply tank valve.
3. Make sure control knob of fireplace is in the
OFF position.
4. Check all joints from equipment shutoff valve
to gas control valve
. Apply noncorrosive leak
detection fluid
to all joints. Bubbles forming
show a leak.
5. Correct all leaks at once.
6. Light fireplace (see
Operating Fireplace
, page
7. Turn off fireplace (see
To Turn Off Gas to
Appliance
).
1
9
.
Check all other internal joints for leaks.
1
7
Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1.
Close equipment shutoff valve (see Figure
8
).
IMPORTANT: The appliance must be isolated
from the gas supply piping system by closing
its equipment shutoff valve during any
pressure testing of the gas supply piping
system at test pressures equal to or less than
1/2 psi (3.5 kPa).
CAUTION:
V
erify proper operation
after servicing.
1. IMPORTANT: The appliance and its
appliance main gas valve must be
disconnected from the gas supply
pipingsystem during any pressure
testing of that system at test pressures
in excess of 1/2 psi (3.5 kPa).