• No objects (e.g., front of the door) must project into the warm air flow
above the air outlet of the fireplace insert.
2.5.1 CUTOUT DIMENSIONS FOR BURNER
L = Length of the cutout
B = Width of the cutout
H = Height of the cutout
M = required supply air cross in cm²
Built in with wick burner:
model
L (cm)
B (cm)
H (cm)
M (cm²)
Quadra Inside I SL
70
25
20
200
Quadra Inside II SL
120
25
20
400
Quadra Inside III SL
175
25
20
600
Built in with automatic burner:
model
L (cm)
B (cm)
H (cm)
M (cm²)
Quadra Inside Automatik I SL
70
25
20
200
Quadra Inside Automatik II SL
120
25
20
400
Fig. 1
Mounting wall (non-combustible)
Thermal insulation, min. 40 mm
(vermiculite / calcium silicate)
Collimator (only on the Chelsea model)
Burner
(wick or automatic burner)
Safety glass
Air intake opening
Fig. 2
• The front cladding surfaces (especially above the fireplace insert) must
be heat resistant up to 65°C.