Design B
Inlet and recirculating air apertures must be created in the fireplace. At
least 50% of all indicated openings must not be closable.
Linear cassette
XS 500
S 600
M 700
L 800
XL 900
Recirculating air
openings in cm²
220
400
400
640
880
Primary air
openings in cm²
450
450
450
730
960
Combustion chamber spacings
Linear cassette
Setup floor
Mounting wall
Ceiling
Side wall
XS 500
40 mm
60 mm
200 mm
60 mm
S 600
40 mm
60 mm
200 mm
60 mm
M 700
40 mm
60 mm
200 mm
60 mm
L 800
40 mm
60 mm
200 mm
60 mm
XL 900
40 mm
60 mm
200 mm
60 mm
Rock wool mats to AGI Q-132)
Linear cassette
Setup floor
Mounting wall
Ceiling
Side wall
XS 500
0 mm
50 mm
50 mm
60 mm
S 600
0 mm
160 mm
120 mm
80 mm
M 700
0 mm
150 mm
110 mm
90 mm
L 800
0 mm
150 mm
130 mm
90 mm
XL 900
0 mm
140 mm
130 mm
70 mm
The distance between the fireplace cassette and the insulation must be 60
mm all the way around the fireplace cassette. Insofar as the adjacent con-
struction components are not combustible or load-bearing then the distance
can be reduced to 10 mm. The heat insulation thicknesses are valid for hot
air systems.
Installation situation Installation situation A
Installation situation Installation situation B