and the airflow volume of the ventilation systems do not cause low pres-
sure less than 0.04 mbar in the installation room used for the open
fireplace and any combined rooms providing ventilation.
Fireplace cassettes may not be installed in:
• Stairwells, except in residential buildings with no more than two
apartments.
• Hallways that are generally accessible
• Garages
• Rooms in which highly flammable or explosive materials or mixtures are
processed, stored or manufactured in such volumes that danger may
result from them exploding or becoming inflamed. Fireplace cassettes
may not be installed in rooms or apartments that are vented using venti-
lation systems or hot air heating systems with the aid of fans, unless the
safe operation of the fireplace cassette is guaranteed.
2.2.2 MULTIPLE INSTALLATIONS
It is possible to have multiple installations connected to a chimney in
accordance with DIN 18160 because the fireplace cassettes are fitted with
a self-closing firebox door (A1). All of the fireplaces connected to a chimney
must also have been approved for multiple installations!
2.3 TECHNICAL DATA & DIMENSION SHEETS
The following information has been taken from the testing report and cor-
responds to the testing conditions!
Fireplace
cassette
XS 500
S 600
M 700
L 800
XL 900
Technical
data:
Unit
D4
E4
D5
E5
D6
E7
D8
E10
D11
E 14
Type of fuel:
-
Firewood
Room thermal
output:
kW*
4,0
4,6
4,9
4,9
5,9
6,9
7,9
9,9
10,5
14,0
Wood feed
quantity:
kg/h
~ 1,2 ~1,4 ~1,5
~1,5 ~1,8 ~2,1 ~2,4
~3,0 ~3,2
~4,2
Thermal output:
kW
4,0-
5,2
4,5-
6,0
4,0-
6,4
4,0-
6,4
4,5-
7,7
4,8-
9
5,5-
10,3
6,9-
12,9
7,4-
13,7
9,8-
15
Efficiency:
%*
> 80
> 79
> 78
CO-emissions at
13% O
2
:
mg/Nm³
< 1250
Dust emissions: mg/Nm³
< 40
Exhaust gas
temperature at
sockets:
°C
252
335
335
370
360
340
330
360
Manometric
pressure:
Pa
12
Exhaust gas
mass flow:
g/s
3,8
4,5
5,0
6,5
9,0
10,0
12,0
Combustion air
requirement
m³/h
12,6
15,5
16,2 16,6 20,2
26,4
34,3
40,3
Weight depend-
ing on design
kg
50
80
95
110
130
Power supply
(only with hot air blower)
-
230V 50 HZ AC
Requirements:
1. level of BlmSchV.
2. level of BlmSchV.
EN 13240
DIN Plus
Regensburg
München
Aachen
15a (for Austria)
Clean Air Ordinance from
01.2011 (for Switzerland)
* The values given represent the average recorded from multiple fires. These values were recorded under test
conditions without the hot air blower being switched on.
Summary of Contents for L 800
Page 1: ...GB Installation and Operating Instructions Linear Fireplace Cassettes...
Page 34: ...GB 34 NOTES...
Page 35: ...GB GB GB 35...