background image

- 57 - 

 

Risk of oxygen corrosion: 

Constant presence of air in the fireplace insert is due to a leak in the 
customer’s upstream pipework or incorrect positioning/dimensioning of the 
expansion vessel (diaphragm expansion 
vessel). 

4. Operation 

 

For operation, please refer also to the notes in the operating manual for 
our fireplace insert. The notes in this installation and operating manual 
relate to specific operation of a fireplace insert with integrated water heat 
exchanger. 
 

  Generally speaking, the combustion chamber door must be used 

as a door that closes automatically. The door may only be opened 
to add firewood or, when cold, for cleaning. Tampering with the 
closing device is not permitted. 

CAUTION: The protective glove supplied is designed 
only for protection from heat when operating the con-
trol handle and the cold hand. The glove is not fire-
proof! 

 

 

 

There must be at least 80 cm between combustible compo-
nents/furniture and the glass! 

  The fireplace insert is designed for burning dry, natural firewood 

with the bark still on, as well as wood briquettes. No other fuels 
may be used

  Operation partially fuelled will result in low flue gas temperatures. 

This may lead to chimney damage if the H

2

O fireplace insert is 

operated permanently with unsuitable chimney systems. For this 
reason we recommend that the quantity of wood added per hour 
during a day’s use does not drop below 2.0 kg.

 

  The thermally actuated flue gas valve integrated in the heat ex-

changer of the H

2

O fireplace insert automatically controls opera-

tion of the latter. When the flue gas temperature is sufficiently high 
(approx. 150°C), the flue gas valve closes automatically. This de-
flects the flue gas flow through the heat exchanger. When the flue 
gas temperature falls below this temperature again, the flue gas 
valve opens. For improved efficiency of the heat exchanger, the 

- 58 - 

H

2

O fireplace insert should be lit and stoked as evenly as possible 

and the fire should not be allowed to subside to embers too often 
if uniform heat discharge from the heat exchanger is to be en-
sured and low chimney temperatures avoided.

 

  Double glazing (IR reflection): Infrared radiation from the combus-

tion chamber is largely reflected by the application of oxidic coat-
ings to the glass surface. These coatings generate a “Newton’s 
Rings” phenomenon (similar to a rainbow), so-called IR reflection. 
Due to this colouring, the characteristic feature of “IR reflection” is 
visible and recognisable. This colouring cannot be removed.

 

  The following conditions are required for operating the fireplace 

insert at nominal heat output. 

  The fireplace insert has been heated up (the wood has already 

been replenished 2-3 times).  

  Combustion must take place with the door closed. 

  Chimney draught:    12 Pa 

  

14 

Pa 

(Varia Ah H

2

O and Varia A-Fdh H

2

O) 

  Wood:  dry beech firewood; (moisture content < 18%) 

  Rate at which wood is added:  see point 1.2 

 Air setting: Around the middle setting; depending on local 

Conditions -

 

may need to be adjusted slightly (see example). 

  For a combustion period of approx. 60 minutes, see point 1.2 

for the total output of the fireplace insert. Example of rate of 

wood addition and air setting for the total output of the fireplace 

insert. 

 

 

 

 

 

 

 

 

 

 

 

Example of rate of wood addition and air setting 

Summary of Contents for Mini Z1 H2O

Page 1: ...on the good name of our firm is inextricably linked to the credo of our owner Gerhard Manfred Rokossa High technical quality combined with modern design and on site customer service carried out to the...

Page 2: ...ncorporation into a heating system 38 2 11 Chimney connection connecting piece 53 2 12 Height limitation door stop 53 3 Initial commissioning 56 4 Operation 57 5 Cleaning and maintenance 59 5 1 Cleani...

Page 3: ...o modifications to the closing device are permitted No additional heat exchangers supplementary heating surfaces etc which 6 extract heat from the flue gas may be incorporated into the connecting pipe...

Page 4: ...O Varia A FDh H 2 O Unit Weight empty without accessories 235 235 245 330 350 380 395 396 kg Nominal output range 4 9 9 1 7 13 7 7 14 3 10 18 7 14 8 27 5 10 3 19 7 3 13 5 7 3 13 5 kW Nominal heat out...

Page 5: ...9 Mini Z1 H2O Fig 1a 10 Mini Z1 H2O XL Fig 1b...

Page 6: ...11 Mini Z1h H2O XL Fig 1c 12 Varia 1V H2O Fig 1d...

Page 7: ...13 Varia 1Vh H2O Fig 1e 14 Varia 1V H2O XL Fig 1f...

Page 8: ...15 Varia 1Vh H2O XL Fig 1g 16 Varia 1V H2O XXL Fig 1h...

Page 9: ...17 Varia 1Vh H2O XXL Fig 1i 18 Varia 2Lh 2Rh H2O Fig 1j...

Page 10: ...19 Varia Ah H2O Fig 1k 20 1 Abgaskuppel 2 separater Verbrennungsluftstutzen 150 mm 3 Luftstellhebel 4 T r klappbar 5 T r hochschiebbar Varia A FDh H2O Fig 1l...

Page 11: ...nstallations must be checked for leaks by means of a pressure test For this purpose the H2O fireplace insert must be aligned horizontally by adjusting the height of the fireplace insert feet or provid...

Page 12: ...any All the work must be carried out according to the VDE Regulations e g VDE 0105 VDE 0116 VDE 0100 etc and the technical connection require ments of the local power supply company 2 3 H2O fireplace...

Page 13: ...ve G feed of overheat discharge valve H rear bleed valve I return J inspection opening Fig 2a 26 Varia 1V H2O Varia 1Vh H2O To facilitate access to the water connections of the Varia 1V H2O an inspect...

Page 14: ...l sensor D bleed valve E return F feed of overheat discharge valve G discharge of overheat discharge valve Fig 2c 28 Varia 2Lh 2Rh H2O For access to the water connections of the Varia 2Lh 2Rh H2O an i...

Page 15: ...connections are clearly marked and must not be used for any other purpose The integral safety device safety heat exchanger must not be used to heat water We recommend the use of straight or angled rad...

Page 16: ...1V H2O Varia 1Vh H2O Varia 1V H2O XL Varia 1Vh H2O XL Varia 1V H2O XXL Varia 1Vh H2O XXL 600 cm 750 cm Varia 2Lh 2Rh H2O 600 cm 750 cm Varia Ah H2O 440 cm 400 cm Varia A FDh H2O 220 cm 200 cm Generall...

Page 17: ...safety device from operating Furthermore all the required safety devices must be integrated throughout the system in such a manner as to ensure non hazardous operation A separate safety valve must sti...

Page 18: ...ks at any time The discharge of the overheat discharge valve must be executed in such a manner that a test may be carried out at any time e g via an outlet with siphon 36 2 9 Thermal pump control syst...

Page 19: ...cted phase L blue wire 2 10 Incorporation into a heating system Please note The H2O fireplace insert may only be installed in a complete system after detailed planning for the entire heating system ac...

Page 20: ...ire storage tank takes just under 2 hours On very cold winter days the fireplace system may be in operation for as much as 12 hours or so The thermal energy produced in such a case is then theoretical...

Page 21: ...for the thermostat switch C feed D safety valve 3 bar E bleed valve F pump thermostat switch e g JUMO heatTHERM G Load unit H load unit fittings e g ESBE type LTC 141 I circulating pump J filling and...

Page 22: ...sor for the thermostat switch D safety valve 3 bar E return F pump thermostat switch eg JUMO heatTHERM G return H load unit fittings e g ESBE type LTC 141 I circulating pump J filling and drain fittin...

Page 23: ...valve B temperature sensor for the thermostat switch C safety valve 3 bar D bleed valve E pump thermostat switch eg JUMO heatTHERM F return G load unit fittings e g ESBE type LTC 141 H circulating pum...

Page 24: ...D return E discharge from overheat discharge valve F supply to overheat discharge valve G safety valve 3bar H bleed valve I pump thermostat switch eg JUMBO heatTHERM J return K load unit fittings e g...

Page 25: ...ermal safety heat exchanger discharge F Thermal safety heat exchanger feed G bleed valve 3 8 H safety valve I bleed valve 3 8 J pump thermostat switch e g JUMO heatTHERM K heating system connection L...

Page 26: ...valve I bleed valve 3 8 J pump thermostat switch e g JUMO heatTHERM K heating system connection L load unit M return N load unit fittings e g Thermoventiler AB type Laddomat 21 O circulating pump P fi...

Page 27: ...ening height is reduced by 50 mm If the opening height is to be further reduced reduction in opening height by 100 mm or increased maximum opening the stops on both sides of the door must be converted...

Page 28: ...and the vermiculite are slowly tempered and the moisture from any storage transport etc slowly evaporated off If this is not done the area between the glass panes may be contaminated and the fireclay...

Page 29: ...s opera tion of the latter When the flue gas temperature is sufficiently high approx 150 C the flue gas valve closes automatically This de flects the flue gas flow through the heat exchanger When the...

Page 30: ...and if our recommendations are followed the cleaning intervals can be significantly extended After the end of the heating season thorough cleaning of all the components is required The heat exchanger...

Page 31: ...nt them in the commission ing log In the event of a claim evidence of the maintenance work carried out must be submitted to the service personnel 62 6 Troubleshooting Note The fireplace must not be us...

Page 32: ...ween the manufacturer Spartherm Feuerungstechnik GmbH and the dealer intermediary They are not the same as the contract and warranty terms and conditions which the dealer intermediary passes on or may...

Page 33: ...ur or other aspects due to thermal stress improper transport and or incorrect storage 66 improper handling of fragile components such as glass and ceramics improper handling and or use lack of mainten...

Page 34: ...em bled Yes No Working pressure checked Yes No System tested for leaks Yes No All safety devices overheat discharge valve safety valve diaphragm expansion vesssel tested Yes No Please enter temperatur...

Reviews: