- 61 - 

on the side where the glass is.  
 
 

5.2. Cleaning the double glazing 

 

If the fireplace insert is fitted with double glazing, cleaning may be carried 
out by the operator only on the combustion chamber side and on the side 
facing the room in which it is installed, as indicated in the operating 
manual. If the internal panes within the glazing vacuum are dirty, cleaning 
may only be carried out by customer service or a trained specialist 
company. 
 
 

 

5.3  Maintenance of the heat exchanger 

 

The hydraulic pressure of the heating system must be checked at regular 
intervals during the heating season. The H

2

O fireplace insert may only be 

operated when completely filled and bled. 
 
A heating inspection of all the safety devices (overheat discharge valve, 
safety valve, etc.) and the other components must be carried out annually 
before the heating season. The notes in the installation and operating 
manuals of the respective component manufacturers must be adhered to. 
This check may only be carried out by a specialist company which is able 
to ensure proper functionality of the individual components. We recom-
mend that you sign a service contract with your specialist company. The 
annual safety test (e.g. functional testing of the overheat discharge valve, 
the pump thermostat, safety valve, expansion vessel, etc.) should be 
carried out before the heating season. On performing the annual safety 
checks, your specialist company must document them in the commission-
ing log. In the event of a claim, evidence of the maintenance work carried 
out must be submitted to the service personnel. 
 
 
 
 
 
 
 

- 62 - 

6. Troubleshooting 

 

Note: The fireplace must not be used as a waste incinerator. Furthermore 
it is intended for non-continuous use. Nor can continuous combustion be 
achieved by extracting combustion air – attempting to do this is not 
permitted. 
 

You can remedy the following problems yourself: 
 

Description of problem 

Solution 

Overheat discharge valve 
keeps cutting in (constant 
water outflow through the 
outlet). The water heat 
exchanger cannot 
discharge heat to the 
heating system. 
 

 

The buffer storage tank is “full”. 

 

Extract heat from storage tank 

 

Check operation and setting of the 

 

pump thermostat and load unit 

 

Set pump one increment higher 

 

(greater flow rate). 

 

Circulating pump not running. Pump 

 

or power connection defective? 

  Return temperature too high, 

 

< 70°C. 

 

Check whether shutoff devices are 

 stuck. 

 

Sufficient heating water present? 

Overheat discharge valve 
dripping.  

  Contamination of the overheat 

discharge valve. 

 

Flush the overheat discharge valve 
by pressing the red cap on the fit-
ting. 

 

Inspect the seat of the connection 
seals and pistons (see manufactur-
er’s manual). 

  Where necessary, fit filters to the 

system upstream of the safety de-
vice (make sure minimum flow is 
maintained) 

Gurgling noises, boiling 
noises in the water-carrying 
parts of the H

2

O cell (air in 

the system) 

 

Check system pressure 

 

Bleed the system at the bleed valve. 
In the case of newly filled or topped 
up systems it will take some time for 
all the air to escape. A single bleed 
operation is often not sufficient. 

Summary of Contents for Mini Z1 H2O

Page 1: ...on the good name of our firm is inextricably linked to the credo of our owner Gerhard Manfred Rokossa High technical quality combined with modern design and on site customer service carried out to the...

Page 2: ...ncorporation into a heating system 38 2 11 Chimney connection connecting piece 53 2 12 Height limitation door stop 53 3 Initial commissioning 56 4 Operation 57 5 Cleaning and maintenance 59 5 1 Cleani...

Page 3: ...o modifications to the closing device are permitted No additional heat exchangers supplementary heating surfaces etc which 6 extract heat from the flue gas may be incorporated into the connecting pipe...

Page 4: ...O Varia A FDh H 2 O Unit Weight empty without accessories 235 235 245 330 350 380 395 396 kg Nominal output range 4 9 9 1 7 13 7 7 14 3 10 18 7 14 8 27 5 10 3 19 7 3 13 5 7 3 13 5 kW Nominal heat out...

Page 5: ...9 Mini Z1 H2O Fig 1a 10 Mini Z1 H2O XL Fig 1b...

Page 6: ...11 Mini Z1h H2O XL Fig 1c 12 Varia 1V H2O Fig 1d...

Page 7: ...13 Varia 1Vh H2O Fig 1e 14 Varia 1V H2O XL Fig 1f...

Page 8: ...15 Varia 1Vh H2O XL Fig 1g 16 Varia 1V H2O XXL Fig 1h...

Page 9: ...17 Varia 1Vh H2O XXL Fig 1i 18 Varia 2Lh 2Rh H2O Fig 1j...

Page 10: ...19 Varia Ah H2O Fig 1k 20 1 Abgaskuppel 2 separater Verbrennungsluftstutzen 150 mm 3 Luftstellhebel 4 T r klappbar 5 T r hochschiebbar Varia A FDh H2O Fig 1l...

Page 11: ...nstallations must be checked for leaks by means of a pressure test For this purpose the H2O fireplace insert must be aligned horizontally by adjusting the height of the fireplace insert feet or provid...

Page 12: ...any All the work must be carried out according to the VDE Regulations e g VDE 0105 VDE 0116 VDE 0100 etc and the technical connection require ments of the local power supply company 2 3 H2O fireplace...

Page 13: ...ve G feed of overheat discharge valve H rear bleed valve I return J inspection opening Fig 2a 26 Varia 1V H2O Varia 1Vh H2O To facilitate access to the water connections of the Varia 1V H2O an inspect...

Page 14: ...l sensor D bleed valve E return F feed of overheat discharge valve G discharge of overheat discharge valve Fig 2c 28 Varia 2Lh 2Rh H2O For access to the water connections of the Varia 2Lh 2Rh H2O an i...

Page 15: ...connections are clearly marked and must not be used for any other purpose The integral safety device safety heat exchanger must not be used to heat water We recommend the use of straight or angled rad...

Page 16: ...1V H2O Varia 1Vh H2O Varia 1V H2O XL Varia 1Vh H2O XL Varia 1V H2O XXL Varia 1Vh H2O XXL 600 cm 750 cm Varia 2Lh 2Rh H2O 600 cm 750 cm Varia Ah H2O 440 cm 400 cm Varia A FDh H2O 220 cm 200 cm Generall...

Page 17: ...safety device from operating Furthermore all the required safety devices must be integrated throughout the system in such a manner as to ensure non hazardous operation A separate safety valve must sti...

Page 18: ...ks at any time The discharge of the overheat discharge valve must be executed in such a manner that a test may be carried out at any time e g via an outlet with siphon 36 2 9 Thermal pump control syst...

Page 19: ...cted phase L blue wire 2 10 Incorporation into a heating system Please note The H2O fireplace insert may only be installed in a complete system after detailed planning for the entire heating system ac...

Page 20: ...ire storage tank takes just under 2 hours On very cold winter days the fireplace system may be in operation for as much as 12 hours or so The thermal energy produced in such a case is then theoretical...

Page 21: ...for the thermostat switch C feed D safety valve 3 bar E bleed valve F pump thermostat switch e g JUMO heatTHERM G Load unit H load unit fittings e g ESBE type LTC 141 I circulating pump J filling and...

Page 22: ...sor for the thermostat switch D safety valve 3 bar E return F pump thermostat switch eg JUMO heatTHERM G return H load unit fittings e g ESBE type LTC 141 I circulating pump J filling and drain fittin...

Page 23: ...valve B temperature sensor for the thermostat switch C safety valve 3 bar D bleed valve E pump thermostat switch eg JUMO heatTHERM F return G load unit fittings e g ESBE type LTC 141 H circulating pum...

Page 24: ...D return E discharge from overheat discharge valve F supply to overheat discharge valve G safety valve 3bar H bleed valve I pump thermostat switch eg JUMBO heatTHERM J return K load unit fittings e g...

Page 25: ...ermal safety heat exchanger discharge F Thermal safety heat exchanger feed G bleed valve 3 8 H safety valve I bleed valve 3 8 J pump thermostat switch e g JUMO heatTHERM K heating system connection L...

Page 26: ...valve I bleed valve 3 8 J pump thermostat switch e g JUMO heatTHERM K heating system connection L load unit M return N load unit fittings e g Thermoventiler AB type Laddomat 21 O circulating pump P fi...

Page 27: ...ening height is reduced by 50 mm If the opening height is to be further reduced reduction in opening height by 100 mm or increased maximum opening the stops on both sides of the door must be converted...

Page 28: ...and the vermiculite are slowly tempered and the moisture from any storage transport etc slowly evaporated off If this is not done the area between the glass panes may be contaminated and the fireclay...

Page 29: ...s opera tion of the latter When the flue gas temperature is sufficiently high approx 150 C the flue gas valve closes automatically This de flects the flue gas flow through the heat exchanger When the...

Page 30: ...and if our recommendations are followed the cleaning intervals can be significantly extended After the end of the heating season thorough cleaning of all the components is required The heat exchanger...

Page 31: ...nt them in the commission ing log In the event of a claim evidence of the maintenance work carried out must be submitted to the service personnel 62 6 Troubleshooting Note The fireplace must not be us...

Page 32: ...ween the manufacturer Spartherm Feuerungstechnik GmbH and the dealer intermediary They are not the same as the contract and warranty terms and conditions which the dealer intermediary passes on or may...

Page 33: ...ur or other aspects due to thermal stress improper transport and or incorrect storage 66 improper handling of fragile components such as glass and ceramics improper handling and or use lack of mainten...

Page 34: ...em bled Yes No Working pressure checked Yes No System tested for leaks Yes No All safety devices overheat discharge valve safety valve diaphragm expansion vesssel tested Yes No Please enter temperatur...

Reviews: