E L E C T R I C A L D A T A F O R T H E U S E O F L I C E N S E D E L E C T R I C I A N
WARNING: Shock Hazard! Under No Circumstances Should This Spa Be Installed By Anyone Other
Than A Certified Licensed Electrician!
W A R N I N G ! U S E C O P P E R C O N D U C T O R S
All wiring
MUST
be in accordance with the National Electrical Code and All Local Codes.
Genius Series G-1.5 & G-2 240 Volt Hard Wire Installation
Licensed Electrician
Required
Permanently Hard Wired
Wire Sizing Must Meet
Electrical Codes
A Ground Fault Circuit
Interrupter and a
Disconnect Switch Are
Required.
Leisure Bay GENIUS Series
Spas are NOT EQUIPPED With
A 240v Ground Fault Circuit
Interrupter or a Disconnect
Switch.
Outdoor Load Center
Provides Both
Isolated, Dedicated 240
Volt, 50 Amp Circuit Is
Required
Wiring of the Genius G-2 volt
system must be completed by
a Certified Licensed
Electrician.
All 220 Volt operations wiring
must be permanently hard
wired and installed in grounded
conduit and installed in compli-
ance with the National Electrical
Code and all Local Codes.
All installations are different.
Wire sizing must meet the
National Electrical Code and all
Local Code Specifications.
The National Electrical Code requires that
spas connected to 240 volt circuits be
equipped with a Ground Fault Circuit
Interrupter (GFCI) and Disconnect Switch.
See NEC Articles 680-12 and 680-42.
The addition of a outdoor load
center such as a Siemens
W0408ML 1125 or equal must be
added to the Circuit. This type of
load center provides both a
Ground Fault Circuit Interrupter
and Disconnect Switch in a conve-
nient configurations as required
by the NEC.
An isolated, dedicated 240 Volt, 30 or
50 amp circuit is required to provide
the power necessary to properly oper-
ate the 240v Equipment Package.
For 30 Amp Configuration
See Page 9
CAUTION: CONNECT ONLY TO A CIRCUIT PRO-
TECTED BY A CLASS A GROUND FAULT INTER-
RUPTER. /ATTENTION: CONNECTOR UNIQUEMENT
A UN CIRCUIT PROTEGE PAR UN DISJONCTEUR
DIFFERENTIEL DE CLASSE A.
CAUTION: READ THE INSTRUCTION MANUAL.
/ATTENTION: LIRE LA NOTICE TECHNIQUE.
USE COPPER CONDUCTORS ONLY! / EMPLOYER
UNIQUEMENT DES CONDUCTEURES DE CUIVRE.