background image

93034033 CIMARRON CL1 LED INSTALLATION INSTRUCTIONS (PG 1/2)

SAVE THESE INSTRUCTIONS

WARNING! 

Fixtures must be grounded and installed in accordance with the National Electrical Code and all local codes.  Failure to

do so may increase the

RISK OF PERSONAL INJURY, PROPERTY DAMAGE, FIRE AND DEATH.  Install and use where burnouts do

not cause a hazard and use only in environments for which the product is specifically marked.

WARNING! 

This product contains chemicals known to the State of California to cause cancer, birth defects, and/or other reproductive

harm. Thoroughly wash hands after installing, handling, cleaning, or otherwise touching this product.

CAUTION! 

Follow ALL luminaire recommendations, product markings, instructions, restrictions and warnings regarding lumninaire

operation and burning position.

Luminaire label shows electrical and environmental requirements.

All electrical work must be done by a qualified electrician.

Turn off electric power to all affected circuits and allow to cool before servicing.

A regularly scheduled maintenance program should be established to retain optimum light output and reduce heat retention. Dusting
with a soft, clean, dry cloth is normally sufficient.  Any accumulation of dust or dirt should be removed regularly from the lens. Use only a
mild soapy solution, DO NOT use alkaline or acid cleaners.

Carefully read these instructions before installing product.  If you do not understand these instructions, before starting any work, contact
your Hubbell Lighting distributor or techsupport@hubbell-ltg.com or (864) 678-1000

Give instructions to facility owner/manager for future reference.

701 Millennium Boulevard Greenville, SC 29607 (864) 678-1000

www.spaulding-ltg.com

CIMARRON LED FIXTURE INSTALLATION

NOTE:  IT IS NOT NECESSARY TO OPEN THE FIXTURE FOR INSTALLATION.

  

THE 

FIXTURE HAS BEEN DESIGNED TO BE INSTALLED BY REMOVING THE ARM 
MOUNTING COVER ONLY.     

WARNING: DISCONNECT POWER BEFORE INSTALLATION 

CAUTION: FIXTURE WEIGHS ABOUT 50 POUNDS   

  

1. MOUNTING PREPARATION (See Fig. 1) 

 

Remove Arm Cover by removing the (4) Screws. 

 

Remove Pole Cover  

 

Pull the supply wires from Pole through Nut Plate 

and into the Arm.  

2. MOUNTING FIXTURE TO POLE 

 

Attach Fixture to Pole with (2) ½” Hex Bolts,  

  Lockwashers and Flatwashers into Nut Plate inside pole. 

 

Torque Bolts to approx. 45 Ft-Lbs.   

COVER- SQ POLE

NUT PLATE

SQUARE

ROUND
POLE

COVER- RND POLE

POLE

STRAIGHT SQUARE AND

 

ROUND POLES

FIGURE

 

1

ARM

CAST
ADPTOR

SCREW

FLAT WASHER

HEX BOLT

LOCKWASHER

COVER

FIGURE

 

2

ARM

 

COVER

 

REMOVED

SECURE WIRE
INSIDE POLE

SUPPLY WIRES

POLE

ARM

FIXTURE WIRES

3.

 

WIRING (See Fig.

 

2)

  

POWER MUST BE OFF. 

(WIRING MUST BE PERFORMED BY A QUALIFIED ELECTRICIAN) 

 

Wire service leads to fixture power leads according to local 

   and National Electric Codes. 

 

Luminaire is equipped with universal voltage drivers capable of    

120V-277V input.  An optional 347/480 V input transformer is 
available. 

 

Wire connections to be made inside Arm with Fixture Wires and 

Supply Wires (By others).  Secure Wire inside Pole. 

 

For direct wire connections, connect ground wire to green wire, 

connect black to black and white to neutral then push connections 
back inside Arm and attach Arm Cover. 

 