Be sure that valid time and 1PPS references are currently selected (go to
MANAGEMENT/OTHER/Time Management
).
In order to operate properly as a Master Clock, NetClock must be synchronized to a non-PTP
reference. Confirm that the chosen reference transmits the following information (as reported
by the Time Properties on the
PTP Status
page, under the
Advanced
tab):
The proper TAI or UTC time (including the current year)
The current TAI to UTC offset (required even if the reference’s time is in TAI)
Pending leap second information at least a day in advance.
If the reference does not transmit this information, it must be provided by the user in order for
the Master Clock to function properly.
The built-in GNSS reference provides all information needed with no user intervention.
5.2.7.5
Configuration — PTP-Specific Steps
Confirm that:
The PTP Port Activity is enabled (check the
Port Status
on the
PTP Status
page under the
Advanced
tab). If not, enable it from the
Port Activity
of the
PTP Setup/Network
page).
The clock is set to be a Master-Only clock (check the
Clock Mode
on the
PTP Setup/C
lock
page).
A valid IP address is currently being used (check the
Ethernet Settings
on the
PTP
Setup/Network
page).
When the PTP Module is set to be a Master Clock, the module will immediately attempt to
become the active Master Clock on the network (
PTP Port State
=
Master
). If it does, it will start
to transmit PTP packets (even if NetClock is not yet synchronized).
There are several reasons why the PTP Module may not become the active Master Clock, or
may not be broadcasting the correct time, even if it is set to be a Master Clock:
a.
If using any reference other than self for 1PPS, NetClock will not become an active
Master Clock until the
Time Figure of Merit (TFOM)
value of the system is less than 15.
After first going into sync after power-up, it may take a minute or two for the Time Figure
of Merit (TFOM) value to fall to an acceptable level. The current Time Figure of Merit
(TFOM) value is available in the Time Properties panel under the
Advanced
tab on the
Status
page.
b.
PTP uses the TAI timescale to transfer time. Many timing references communicate time in
the UTC timescale. UTC is offset from TAI by a small amount which changes every time a
leap second occurs. The TAI to UTC Offset is part of the PTP Specification and must be
376
NetClock User Reference Guide
APPENDIX
Summary of Contents for NetClock 9400 Series
Page 2: ......
Page 4: ...Blank page II NetClock User Reference Guide...
Page 16: ...BLANK PAGE XIV NetClock User Reference Guide TABLE OF CONTENTS...
Page 42: ...BLANK PAGE 1 11 Regulatory Compliance 26 CHAPTER 1 NetClock User Reference Guide Rev 16...
Page 160: ...BLANK PAGE 2 17 Configuring Outputs 144 CHAPTER 2 NetClock User Reference Guide Rev 16...
Page 238: ...BLANK PAGE 3 5 Managing the Oscillator 222 CHAPTER 3 NetClock User Reference Guide Rev 16...
Page 462: ...BLANK PAGE 446 NetClock User Reference Guide...