22
Temperature Correction Factor Table (TCF)
°F /°C
TCF
°F /°C
TCF
°F /°C
TCF
41.0 /5
0.521
59.0 /15
0.730
77.0 /25
1.000
42.8 /6
0.540
60.8 /16
0.754
78.8 /26
1.031
44.6 /7
0.560
62.6 /17
0.779
80.6 /27
1.063
46.4 /8
0.578
64.4 /18
0.804
82.4 /28
1.094
48.2 /9
0.598
66.2 /19
0.830
84.2 /29
1.127
50.0 /10
0.620
68.0 /20
0.857
86.0 /30
1.161
51.8 /11
0.640
69.8 /21
0.884
87.8 /31
1.196
53.6 /12
0.661
71.6 /22
0.912
89.6 /32
1.232
55.4 /13
0.684
73.4 /23
0.941
91.4 /33
1.267
57.2/14
0.707
75.2 /24
0.970
93.2 /34
1.304
Membrane Output Calculation Example
What is the expected GPD from a 100 GPD System at 40 psi pressure and
60°F water temperature?
PCF = 40 ÷ 60 = 0.666
TCF = 0.754 (from Table above)
Expected GPD = 100 × 0.666 × 0.754 = 50.2 GPD ± 15%
50.2 GPD would be the Actual Production Rate
TIPS FOR LONG MEMBRANE LIFE:
1. Replacement of sediment filter at least once every 6 months.This will
prevent mem brane fouling due to silt or sediment depositing on the
membrane.
2. Replacement of carbon block filter at least once every 6 months or
when chlorine breakthrough occurs. This will ensure good membrane
life and protect the membrane from chlorine damage.
3. Membrane should not be operated at lower than the minimum 2:1
concentrate to purified water ratio.
4. Operating reverse osmosis systems on softened feed water greatly
reduces the chances of membrane fouling.