Table 2-2: Terminal box
Terminal
Function
T1
24 Vdc (+)
T2
24 Vdc (-)
T3
External built-in test (BIT) switch
T4
Fault relay - normally open
T5
Fault relay
T6
Fault relay - normally closed
T7
Alarm relay - normally open
T8
Alarm relay
T9
Alarm relay - normally closed
T10
0-20 mA (+)
T11
0-20 mA (-)
T12
Alarm output
(40/40D models)
T13
RS485 (+)
T14
RS485 (-)
T15
Accessory relay - normally open
T16
Accessory relay
T17
Accessory relay - normally closed
2. Use
, and
for typical wiring