1-4
Chapter 1, Module Overview
User’s Manual Pub. 0300322-01 Rev. A
Table 1-1. Input/Performance/Environmental Requirements
Input Specifications
Value
Operating Temperature
-20 ºC to 65 ºC (-4 ºF to 149 ºF)
Storage/Non-Operating
Temperature
-40 ºC to 85 ºC (-40 ºF to 185 ºF)
Operating Humidity
5% to 95%, non-condensing
Storage/Non-Operating
Humidity
5% to 85%, non-condensing
Vibration/Operating
10 Hz to 500 Hz, 2 G, 0.030 max peak-to-peak
Operating Shock
25 G, peak acceleration, 11±1 ms pulse, half sine
Storage/Non-Operating
Shock
25 G peak acceleration, 11±1 ms pulse, half sine; 35 g for
panel mount.
Pollution Level
Meets Pollution Degree 2 requirements.
ESD
6kV Indirect (Coupling Plate)
6kV Contact Discharge (to points of initial contact)
8kV Air Discharge (to points of initial contact)
Radiated Immunity
10 V/M with 200 Hz square-wave 50% Pulse 100% AM at
900 and at 1890 MHz
10 V/M with 1 kHz sine-wave 80% AM from 80…2000
MHz
3 V/M with 1 kHz sine-wave 80% AM from 2000…6000
MHz
Input modes
Thermocouples and millivolt ranges.
Inputs per module (8
channels)
8 thermocouple/ millivolt inputs, and 2 CJC input channels
Inputs per module (16
channels)
16 thermocouples/ millivolt inputs, and 2 CJC input channels
Thermocouple types
J, K, T, E, R, S, B, N and C
Voltage input ranges
±50 mV and ±100 mV
Input filters
4 Hz, 17 Hz, 60 Hz, 470 Hz
Thermocouple accuracy
Specifications only apply to 4
Hz and 17 Hz filters
Error at 25
C, Typical,
Max
Error over -20
C to 65
C
Typical, Max
Type J (-210
C to 1200
C)
±0.4
C, ±0.6
C
±0.5
C, ±1.6
C
Type N -100
C to 1300
C)
±0.4
C, ±0.7
C
±0.5
C, ±1.3
C
Type N (-210
C to -100
C)
±0.8
C, ±1.5
C
±1.0
C, ±2.2
C
Type T -170
C to 400
C)
±0.6
C, ±1.0
C
±0.7
C, ±1.5
C
Type T (-270
C to -170
C)
±3.0
C, ±8.0
C
±.5
C, ±14.0
C
Type K (-170
C to 1370
C)
±1.1
C, ±1.5
C
±1.2
C, ± 2.1
C