Chapter 1: Module Overview
1-7
User’s Manual Pub. 0300322-01 Rev. A
Input Specifications
Value
Fault detection
Over/under range for all types
Open Circuit detection
Note: Thermocouple open circuit (open wire) will be
periodically checked using the PGA burnout current. This
saves on component cost and increases the Voltage Input
impedance.
Wire Installation
Wire size
#16 to #28 AWG
Wire Strip Length
0.375 in.
Recommended Tightening
Torque:
0.25 N-m (2.2 in-lbs.)
Module Dimensions
110 mm × 87 mm × 51 mm (plastic only).
(4.33 in × 3.43 in × 2.00 in)
110 mm × 89 mm × 51 mm (with RTBs installed).
(4.33 in × 3.5 in × 2.00 in)
(CJC adds additional height beyond this)
Table 1-2. Environmental Specification Table
Environmental Tests
Test Limits
Temperature (Operating)
(Performance Criteria A)
-20 ºC to 65 ºC (-4 ºF to 149 ºF)
Temperature
(Non-operating)
(Performance Criteria B)
-40 ºC to 85 ºC (-40 ºF to 185 ºF)
Humidity (Operating)
(Performance Criteria A)
5 to 95% non-condensing
Vibration (Operating)
(Performance Criteria A)
2 G at 10 to 500 Hz, 0.030 in. max. peak-to-peak
Shock (Operating)
(Performance Criteria A)
25 G, 11 ms half-sine (3 mutually perpendicular axes)
Shock (Non-operating)
(Performance Criteria B)
25 G (35 G Panel mount), 11 ms half-sine (3 mutually
perpendicular axes)
Radiated Emissions
(Enclosure) Class A, 30 MHz – 1 GHz
Conducted Emissions
Group 1, Class A (AC Mains), 150 kHz – 30 MHz
ESD immunity
(Performance Criteria B)
6 kV Indirect (Coupling Plate)
6 kV Contact Discharge (to points of initial contact)
8 kV Air Discharge (to points of initial contact)