1-8
Chapter 1, Module Overview
User’s Manual Pub. 0300322-01 Rev. A
Environmental Tests
Test Limits
Radiated RF immunity
(Performance Criteria A)
10 V/M with 200 Hz square-wave 50% Pulse 100% AM at 900
& at 1890 MHz
10 V/M with 1 kHz sine-wave 80% AM from 80…2000 MHz
3 V/M with 1 kHz sine-wave 80% AM from 2000…6000
MHz (10 V/M goal)
EFT/B immunity
(Performance Criteria B)
Signal Ports:
±2 kV at 5 kHz for 5 minutes, Criteria B
Power Ports:
±2 kV at 5 kHz for 5 minutes, Criteria B
Surge transient immunity
(Performance Criteria B)
Signal Ports:
±2 kV line-earth {CM} at 2 Ω on shielded ports
Power Ports
±2 kV CM at 12 Ω
±1 kV DM at 2 Ω
Conducted RF immunity
(Performance Criteria A)
10 VRMS with 1 kHz sine wave 80% AM from 150 kHz…80
MHz on signal and power ports
Magnetic Field
(Performance Criteria A)
30 Arms/m
AC Mains Voltage Dips, Interruptions
and Variations
Follow the 61000-4-11.
Table 1-3. Safety Test Specification Table
Safety Tests
Industry Standards
UL Safety
UL 61010-2-201 Safety Requirements for Electrical Equipment for
Measurement, Control, and Laboratory Use - Part 2-201: Particular
Requirements for Control Equipment (NRAQ, NRAQ7)
cUL CAN/CSA C22.2 No. 61010-1-12 (Safety Requirements for Electrical
Equipment for Measurement, Control,
and Laboratory Use – Part 1: General Requirements)
UL Hazardous
Locations
ULH ANSI/ISA–12.12.01–2007 Nonincendive Electrical Equipment for Use
in Class I, Division 2 Hazardous (Classified) Locations (NRAG)
cULH CSA C22.2 No. 213-M1987 - Non-incendive Electrical Equipment for
use in Class I Division 2 Hazardous Locations - March 1987 (NRAG7)
Temp code T5, Pollution degree 2, gas groups a, b, c, & d
CE EMC Directive
IEC 61131-2 Programmable Controllers: Third Edition 2007-02, Clause 8
IEC 61000-6-2: Generic Industrial Immunity
IEC 61000-6-4: Generic Industrial Emissions