3-14
Chapter 3: Configuring the 2085-IT8-SC/IT-16-SC Using CCW
User’s Manual Pub. 0300322-01 Rev. A
8.
Download the CCW project to controller and start to run the module
operation.
Section 3.5
Software Information
3.5.1
Software Versioning
The software version tracks major and minor revisions for end users.
The shipped software version begins at version 1.1.
Once released, the major revision is typically incremented if new features are
introduced to the product. Otherwise only the minor revision is incremented.
3.5.2
Software Updates
In-field updating of the software by the end user is not supported.
3.5.3
Startup and Factory Default Conditions
After the module boots, and before the initial configuration is received, the
module holds the default configuration as specified in the Configuration
Assembly. There is no input data communication and no signal outputting before
the controller goes into run mode. The initial configuration assumes a default
configuration of Type J TC and the 17 Hz filter using the Engineering Unit ×1
setup.
Module Identity
The following values will be stored in the Vendor ID, Product_Type,
Product_Code, Series_Rev, and Mod_Features arrays:
Parameter
2085-IT8-SC
2085-IT16-SC
Vendor ID
58 (Spectrum Controls) [0×03A]
58 (Spectrum Controls) [0×03A]
Product Type
10 (Analog) [0×0A]
10 (Analog) [0×0A]
Product Code
117
118
Series Rev
50208 [0×C420] (First release
revision is 1.1)
50208 [0×C420] (First release
revision is 1.1)
Module Catalog String 2085-IT8-SC
2085-IT16-SC
3.5.4
Connection Types and Assembly Sizes
The size of each assembly is listed in the table below. Each word takes 2 bytes.
These values are stored in the Mod_Size array:
Table
2085-IT8-SC
Size (words)
2085-IT16-SC
Size (words)
Configuration Assembly
32
64
Input Assembly
17
29
Output
2
2