3-34
Chapter 3: Configuring the 2085-IT8-SC/IT-16-SC Using CCW
User’s Manual Pub. 0300322-01 Rev. A
3.9.2
Module Specific Configuration Errors
If you set invalid configuration values in the PLC, the CCW will generate a
configuration fault. The connection status will be defaulted and disconnected.
Module-Specific configuration errors are listed in the following table:
Fault Code
Extended Fault
Code
Error Description
0xF2Bz*
0×450
General Channel Configuration Error
No additional information
0×410 – 0×41F
Invalid Input Type
The selected Input Type is out of the valid selectable range.
0×420 – 0×42F
Invalid CJC Profile Selection
The selected profile option is out of the valid selectable range.
0×430 – 0×43F
Invalid Process Alarm and Latching
The selected Process Alarm option is out of the valid selectable
range.
0×440 – 0×44F
Invalid Process Alarm Value
Check the Process Alarm Low Value and Process Alarm High
Value for legal ranges. If the module receives any of the
following illegal data, this error is detected. Exception for this
error is both PALV and PAHV are zero.
PALV greater than or equal to PAHV
OR
PAHV greater than Input Type High Limit
OR
PALV greater than Input Type Low Limit
(PALV is the Process Alarm Low Value
PAHV is the Process Alarm High Value)
*: z indicates the slot number of the expansion I/O. If z=0, then the slot number cannot be
identified.
Section 3.10 Technical Assistance
Note that your module contains electronic components which are susceptible to
damage from electrostatic discharge (ESD). An electrostatic charge can
accumulate on the surface of ordinary plastic wrapping or cushioning material
. In
the unlikely event that the module should need to be returned to Spectrum
Controls, please ensure that the unit is enclosed in approved ESD packaging
(such as static-shielding / metalized bag or black conductive container).