Installation:
The installation must be realized in accordance with IEC/EN 60079-14 and/or in accordance
with the national requirements. This equipment must be installed and used only by qualified
personnel, having knowledge concerning electrical equipment for use in potentially
explosive areas containing gas and/or dust. Qualified personnel must have knowledge
regarding the types of explosion protection. This equipment is intended to be used in zone 1,
2, 21 and 22 for groups IIB+H2 and IIIC with temperature class T6 or T85°C, it is necessary to
verify if this equipment is in accordance with the atmosphere where it is installed.
Connections:
Electric parameters power control unit Maximum supply voltage: POE+ IEEE 802.3at/af
The terminals are suitable for solid and stranded wires.- *See wiring Diagram Page
Cable Glands:
The cable entry must be made and installed properly in order not to alter the specific
properties of terminal housing compartment. The connection to the external circuits must be
realized by cable glands or pipe fittings covered by a separate certificate(s). If a cable gland
is not used or an entry is open, the entry must be closed by a stopping plug covered by a
separate certificate. The diameter of the cable gland is cylindrical ISO M20 x 1.5.
This equipment can be used with different voltage and power, the nominal parameters are
specified in the manual.
Cable:
cable must be tested and certified for temperatures of 70°C or higher.
Fiber Cable:
Use a suitably certified optical fiber cable and internal connections shall comply
with requirements of IEC/EN 60079-15
Equipment Modifications:
This equipment must be installed and used in strict accordance with the instructions given in the
user documentation. This equipment contains no user-serviceable components. Unauthorized
equipment changes or modifications will invalidate all applicable regulatory certifications and
approvals.
14
D201-1-Q6055 REV 4 105607312018 D SERIES
INSTALLATION MANUAL REV-1
General Safety and Operating Information: