background image

CJ-200E

6

Model CJ-200E Operating and Maintenance Manual 

Pre-Operation Checklist

•  Check for adequate water and chemical cleaner supply (use only mild cleaners).
•  Check spray nozzles and make sure orifice is not blocked or worn to excess.
•  Check pressure hose for wear or kinks.
•  Check all connections, fittings, screws and fasteners.

Normal Coil Cleaning Operation

1.  The COILJET

®

 is a very versatile machine and has two operational modes. It is equipped 

with an Auto-Shut-Off function. When the trigger is released the pump turns off and comes 

on when the trigger is pulled. Please remember to turn main switch off when done. 

2.  Fill the water and chemical tanks. Before priming the pump, make sure chemical valve is 

fully closed.

3.  The COILJET

®

 is equipped with a two position water valve. Set the chemical valve to the 

“Off” position and set the water valve to “Tank” for on-board water or “Garden Hose”, as 

appropriate.

4.  Plug the 3-prong male GFCI plug into a normal AC power outlet (110-volt, 60 hertz) and 

depress the GFCI reset button. The COILJET

®

 will be ready to operate when you flip the 

power switch to the “On” position.

5.  For best results and maximum self-contained operation time, it is advisable to fully prime the 

pump before normal operation. Remove any nozzle that may be attached to the spray gun. 

Squeeze the spray gun trigger to prime the pump until steady flow of water appears.

6.  NOTE: If you are having trouble priming the pump, make sure the water tank is fully filled 

or garden hose is attached to it, place the unit on a table or support, hold the spray gun 

below the level of the pump and squeeze the trigger until a steady flow of water appears.

7.  When switching between “Garden Hose” and “Tank”, it is best to re-prime the pump.

8.  Fully open the chemical valve (counter-clockwise). Squeeze the spray gun trigger 

repeatedly until chemical is primed.

9.  The COILJET

®

 comes with 2 quick-connect nozzle attachments:

•  Yellow Rinsing Nozzle – a 15° fan-spray high-flow rinsing nozzle.

•  Green Soap Nozzle – a 25° nozzle to apply soap to coils.

10. Attach nozzle to spray gun.

11. Apply water/chemical solution evenly to coils.

12. Close the chemical valve finger tight (clockwise). Do NOT overtighten.

13. If possible, let foaming coil cleaner solution sit for the recommended dwell time (according 

to chemical instructions) to penetrate into coils.

14. Rinse coils with clean water.

15. *NOTE: There may be a ten second delay for the chemical to be removed from the hose.

16. When done using the COILJET

®

, make sure the power switch is in the “Off” position. This is to 

prevent accidental discharge from the spray gun.

17. After shutting off the power, always relieve the pressure by pointing the spray gun lance in 

a safe direction and squeezing the spray gun trigger.

18. Adjust chemical valve to desired dilution ratio (see table below).

Operating Instructions

Chemical Dilution Ratios

Turn Chemical Valve counter-clockwise to open, clockwise to close.

 

Turn 

Open  =   30:1

 

Turns  Open  =   20:1

 

2.5  Turns  Open  =   10:1

Water Sources

The CJ-200E give you the option to use either on-board water supply or garden hose supply.
To use the on-board water supply, turn the knob to the “Tank” position as shown. Fill the tank 
with water, then prime the unit and then equip the nozzle necessary for cleaning. (Please see 
Normal Coil Cleaning Operations for priming instructions).

3  Turn  Open  =   6:1

 

Full 

Open  =   4:1

Summary of Contents for CoilJet CJ-200E

Page 1: ...SpeedClean Innovative Maintenance Tools OPERATING MAINTENANCE INSTRUCTIONS U S Patent 9 381 549 MODEL CJ 200E CoilJet Portable HVAC Coil Cleaning System ...

Page 2: ...reserves the right to improve products Contact the factory for the latest configuration and uses Table of Contents Limited Warranty CJ 200E Limited Warranty 2 Important Safety Instructions 3 Grounding Information 3 Parts Breakdown 5 Common Optional Accessories 5 Operating Instructions 6 Pre Operation Checklist 6 Normal Coil Cleaning Operation 6 Chemical Dilution Ratios 6 Water Sources 6 Warnings 7...

Page 3: ...ix chemicals Mixing incompatible chemicals may cause damage to the unit or cause dangerous life threatening chemical reactions Do not use the unit if it does not operate properly or has been damaged Do not try to service the unit yourself call SpeedClean for assistance Service must be performed only by qualified repair personnel Service performed by unqualified personnel could result in a risk of ...

Page 4: ...onnect the extension cord from the receptacle before disconnecting the product from the extension cord WARNING To reduce the risk of electrocution keep all connections dry and off the ground Do not touch plug with wet hand Wear proper clothing Protect yourself Wear rubber gloves rubber boots etc Wear eye and face protection goggles or face shield Coil cleaning chemicals may cause injuries to the e...

Page 5: ... Quick Connect 7 Spray Nozzles Yellow 15 Fan CJ QDN 15025Y Green Soap Nozzle CJ QDN 2508G 8 8933 ASSEMBLY Chemical Valve Assembly 1 2 3 5 6 4 7 8 90º SPRAY WANDS 8945 24 24 61 cm 8945 36 91 cm 8945 48 48 122 cm 8945 60 60 152 cm 8945 FLEX 24 Flexible 24 61 cm OPTIONAL NOZZLES ACCESSORIES CJ QDN 0003 R Size 3 Pinpoint CJ QDN 90 90 Adapter CJ QDN 45 45 Adapter OTHER ACCESSORIES CJ2 05 115 Motor Pump...

Page 6: ...evel of the pump and squeeze the trigger until a steady flow of water appears 7 When switching between Garden Hose and Tank it is best to re prime the pump 8 Fully open the chemical valve counter clockwise Squeeze the spray gun trigger repeatedly until chemical is primed 9 The COILJET comes with 2 quick connect nozzle attachments Yellow Rinsing Nozzle a 15 fan spray high flow rinsing nozzle Green ...

Page 7: ...0 1 10 GPM 1 5 4 1 liters Pump Positive displacement diaphragm Water Tank 3 3 gallons 12 5 liters Soap Tank 1 75 quarts 1 6 liters Noise Level 66 dBA Dimensions 19 high x 18 wide x 10 deep 48 2 cm x 45 7 cm x 25 4 cm Weight 22 lbs 10 kilos net dry 52 lbs 12 5 liters at 3 3 gallons water and 1 75 quarts 1 6 liters chemical Specifications To use the garden hose water supply turn the knob to the Gard...

Page 8: ...Reset GFCI Motor buzzes but fails to start or does not start at all Problems with pump auto shut off Unit in disuse for extended time Pressure needs to be relieved Contact factory Contact factory Squeeze trigger and relieve pressure water tank not priming air block in the line Prime machine through the garden hose side Prime the tank with the garden hose still attached then take off the garden hos...

Reviews: